Is port 44818 (EtherNet/IP) exposed to the internet?

AdminKit's short answer: if port 44818 on your public IP accepts a connection, an EtherNet/IP controller or adapter may give its identity and take CIP requests from anyone online, because classic EtherNet/IP has no login step unless the device supports CIP Security and it is configured. This guide shows how to test it and close it.

By AdminKit team, Netbase JSC · Updated

Key takeaways

  • Port 44818 is the registered port for EtherNet/IP messaging, the protocol that carries ODVA’s Common Industrial Protocol (CIP) between PLCs, I/O adapters, drives and HMIs. Real-time I/O uses UDP 2222.
  • Classic EtherNet/IP has no login step. A device that does not use CIP Security acts on well-formed requests from any address that can reach it.
  • An exposed 44818 gives away the device’s identity on request and can accept explicit messages that read or change device data, depending on what the device allows.
  • AdminKit’s port check does not test 44818 or 2222. Test 44818 by hand from outside, then remove the path from the internet.

What is listening on port 44818?

EtherNet/IP is an industrial network protocol in which “IP” stands for Industrial Protocol. ODVA’s EtherNet/IP page describes it as relying on standard TCP/IP, supporting UDP for real-time cyclic data, running on standard, unmodified Ethernet, and using CIP for its upper layers. It is common in discrete manufacturing, process plants, automotive, food and beverage, and water. It belongs to the same machine protocols family as Modbus, OPC UA and DNP3, and our glossary entry on EtherNet/IP gives the one-page background.

ODVA’s book-length overview of CIP and the CIP networks, dated February 2016, sets out the ports. All EtherNet/IP devices accept at least two TCP connections on port 0xAF12, which is 44818; that port carries all TCP-based explicit messaging and the encapsulation commands used to set up communication, and some encapsulation commands may also arrive there as UDP datagrams. Port 0x08AE, which is 2222, carries I/O messaging over UDP, unicast or multicast. The IANA registry lists the same two ports, plus port 2221 for EtherNet/IP over TLS and DTLS. These are the kinds of devices that answer on 44818:

DeviceTypical roleWhy it matters if reachable from outside
PLC or programmable automation controllerRuns the control program for a machine or lineIts data and, on some models, its configuration are reached through CIP
Communications module or adapterGives a controller or rack its Ethernet portAnswers for the equipment behind it
I/O adapterExchanges real-time inputs and outputs with a controllerDrives physical outputs from the data it receives
Variable frequency drive or servo driveControls motor speed and motionParameters may be readable or writable over explicit messaging
HMI or engineering workstationTalks to controllers on the plant networkOften the device that needed remote access in the first place
Protocol gatewayBridges EtherNet/IP to Modbus, OPC UA or serial networksOne address can expose several networks

Why does classic EtherNet/IP accept requests without checking who sent them?

EtherNet/IP was designed for plant networks where every device on the wire was assumed to belong there. The same 2016 overview describes how a conversation starts: the RegisterSession command opens an encapsulation session, and the receiving device creates a session handle and returns it in the reply. That handle identifies the session for later messages. Nothing in the exchange asks the sender who it is, and the explicit messages that follow are acted on according to their contents.

That is the general pattern NIST SP 800-82 describes for OT protocols: its list of network vulnerabilities says many OT protocols have no authentication at any level, which opens the door to replaying, modifying or spoofing data and devices, and that integrity checks are not built into most of them.

ODVA’s answer is CIP Security. ODVA describes it as using TLS for TCP-based EtherNet/IP traffic and DTLS for UDP I/O, with device authentication through X.509 certificates or pre-shared keys, message integrity, optional encryption, and user authentication through OpenID Connect or within the device. Its security profiles include an EtherNet/IP Confidentiality Profile, a CIP User Authentication Profile and a Resource-Constrained profile. ODVA also says CIP Security can be deployed in only the zones where the risk is highest. That leaves a practical point for this page: a controller without CIP Security, or one where it is available but not configured, still speaks classic EtherNet/IP. Plant equipment stays in service for many years, so classic links are common.

What can someone do through an exposed port 44818?

The encapsulation commands are the first thing a stranger can send. The commands below come from the ODVA overview and from the EtherNet/IP glossary in ODVA’s Quick Start for Vendors handbook, published in 2008:

Command or serviceWhat it is forWhy it matters on an exposed device
ListIdentityAsks devices to return identity information; software tools use it to browse a networkGives away the device type, vendor, product and revision
RegisterSessionOpens an encapsulation session and returns a session handleThe step before any CIP communication; no credentials are part of it
SendRRDataCarries unconnected explicit messagesRequest and response functions, such as module configuration
SendUnitDataCarries connected explicit messagesThe same, over an established CIP connection
ForwardOpenOpens explicit or I/O connections with their parametersSets up the connections that carry control data

Identity alone is useful to an attacker, because it says which product and firmware revision to look up. The Nmap enip-info script shows how much a single request returns: it sends a Request Identity packet to a device with TCP 44818 open and parses the device type, vendor ID, product name, serial number, product code, revision, status, state and device IP. Beyond identity, what a stranger can change depends on the device, its firmware and the settings the plant has made on it. None of that is decided by a password in classic EtherNet/IP. For the wider picture of industrial control systems and why they differ from office IT, see our ICS/OT glossary entry.

How does an EtherNet/IP device end up reachable from the internet?

Rarely on purpose. These are the usual paths:

  • A remote programming connection. A port forward lets an engineer or machine builder reach a controller’s programming software over the internet, and stays after the job.
  • A cellular router on a machine. Packaged equipment ships with a router for remote support, and that router maps 44818 to the controller inside.
  • A gateway on a public address. A protocol converter sits on a line provisioned with a public IP and no access list.
  • A flat network. The plant network shares a firewall policy with the office, and a broad rule written for another purpose also allows 44818.

How do you read AdminKit’s port check for port 44818?

AdminKit’s open ports check tests the public IP you are browsing from, using TCP connections to a fixed list: 23, 554, 1883, 8883, 502, 7547, 80, 443 and 8080. It also lists BACnet/IP (47808) and CoAP (5683) as not scanned, because they run over UDP. Ports 44818 and 2222 are not on that list, so the check says nothing about EtherNet/IP either way. Confirm the address you are testing first with what is my IP.

Read a port check result from a plant that runs EtherNet/IP like this:

What the result showsWhat it tells you about EtherNet/IP
“0/9 TCP port(s) open” with an OK statusOnly the nine listed TCP ports were tested. Port 44818 may still be reachable
502 (Modbus/TCP) openA Modbus device on the same site answers from outside. Run the Modbus check and test 44818 as well
80, 443 or 8080 openA device, module or router web interface is exposed. Close it, and test 44818 too

AdminKit’s Modbus exposure check checks whether the public IP you are connecting from has a Modbus/TCP industrial device reachable from the internet on port 502 by default, reading back only the device’s own identity. It speaks Modbus, not EtherNet/IP, so it is not an EtherNet/IP test.

How do you confirm port 44818 from outside?

Use a machine outside the plant’s network, such as a laptop on a mobile hotspot, and test only your own public address. A TCP connection test is enough to show the exposure, and it sends no EtherNet/IP at all (a documentation address is shown):

nc -vz -w 3 203.0.113.40 44818

A “succeeded” or “open” reply means something accepted a TCP connection on 44818 from the internet. A refusal or a timeout means the port is closed or filtered on that path. If you want to see what a stranger learns, the Nmap script above sends one identity request and nothing else; run it only against your own address:

nmap -Pn -p 44818 --script enip-info 203.0.113.40

If it prints your controller’s product name and serial number, anyone can read the same. UDP 2222 has no handshake, so an outside probe cannot tell an open port from a filtered one; check the router’s forwarding table for it instead. Do not send other CIP requests to production equipment as a test.

How do you find the listener inside the network?

An outside test shows that something answers; it doesn’t say which device. Work from the edge inward:

  1. On the site router or firewall, list inbound rules and port forwards for TCP and UDP 44818 and UDP 2222. Note the internal address each one points to, and who asked for it.
  2. If the address is a PC or gateway, find what is bound to the port. On Linux:
$ ss -tulnp | grep 44818
tcp LISTEN 0 5 0.0.0.0:44818 0.0.0.0:* users:(("enip-gw",pid=517,fd=6))

The output above is illustrative; the process name will be whatever your gateway software is called. On a Windows host, Get-NetTCPConnection -LocalPort 44818 in PowerShell shows the listening process ID.

  1. If the address is a controller or module, look it up in the asset list and ask the engineer or machine builder responsible why it has a public path.

How do you fix an exposed port 44818?

Take the controller off the internet first, then harden what remains:

  1. Remove the port forward or public address for 44818, 2222 and 2221. Re-run the outside test and keep the dated result.
  2. Give remote engineers a private path. Use a VPN that ends in a DMZ or a jump host, with multi-factor authentication, so EtherNet/IP never crosses the open internet. NIST SP 800-82 lists a DMZ architecture, multi-factor authentication for remote access, and disabling unused ports and services among its defense-in-depth practices.
  3. Restrict who may talk to controllers. Allow 44818 only from the HMIs, engineering workstations and controllers that need it.
  4. Use CIP Security where devices support it. Ask vendors which profiles their devices implement and plan certificate management with the integrator.
  5. Watch the traffic. The Suricata ENIP/CIP keywords let rules match the encapsulation command, such as list_identity, and the CIP service, so identity sweeps and unexpected writes from outside addresses can raise an alert.

Factories often run OPC UA servers next to EtherNet/IP controllers; see is port 4840 (OPC UA) exposed for that port, and is Modbus TCP (port 502) exposed for Modbus. If engineers and vendors need remote access to plant systems without an inbound port, OT Remote Access is a Netbase custom engagement that gives outbound-only, recorded sessions; see factories and facilities for the related checks and services.

Which networks may you test?

Every check this page links to is for assets you own or are explicitly authorized to test. Never scan, probe, or attempt to connect to a network or device you don’t control. AdminKit’s active checks only ever run against the IP making the request or an asset you’ve verified ownership of. See our Disclaimer and Acceptable Use Policy for the full terms.

This guide is general information, not a security audit of your specific network — see our disclaimer for what AdminKit's guidance does and does not commit to.

Frequently asked questions

What is port 44818 used for?

Port 44818 is the port IANA registers for EtherNet/IP messaging on TCP and UDP. ODVA's overview of CIP says every EtherNet/IP device accepts TCP connections on it for explicit messaging and encapsulation commands, while real-time I/O uses UDP port 2222. IANA also lists port 2221 for EtherNet/IP over TLS and DTLS.

Does EtherNet/IP check who sends a request?

Not in its classic form. A session starts with a RegisterSession command that returns a session handle, and nothing in that exchange identifies the sender. ODVA's CIP Security extension adds device authentication with X.509 certificates or pre-shared keys, message integrity, optional encryption and user authentication, on devices that support it and where it is configured.

Does AdminKit's port check test port 44818?

No. The port check tests a fixed list of nine TCP ports (23, 554, 1883, 8883, 502, 7547, 80, 443, 8080) on the public IP you connect from, and lists two UDP ports as not scanned. Ports 44818 and 2222 are not on that list, so a clean result says nothing about EtherNet/IP. Test 44818 manually from outside your network.

Can I use AdminKit's Modbus check for an EtherNet/IP device?

No. The Modbus exposure check speaks Modbus/TCP, port 502 by default, and reads back a Modbus device identity. EtherNet/IP is a different protocol, so that check is not an EtherNet/IP test. Use it for Modbus devices on the same site and test port 44818 separately.

Is CIP Security a reason to leave port 44818 open?

No. ODVA describes CIP Security as one layer of a defense-in-depth architecture, so that a device can protect itself if another layer fails. It is not a replacement for keeping controllers off the internet, and NIST SP 800-82 recommends segmentation, a DMZ and multi-factor authentication for remote access as well.